5.2 Function Codes Table
5-22
Code
Name Data setting range
Change when running
Data copying
Factory
Default
(Slip compensation gain for
(Slip compensation response
time)
(Slip compensation gain for
braking)
(Magnetic saturation factor 1)
*5
(Magnetic saturation factor 2)
*5
(Magnetic saturation factor 3)
*5
(Magnetic saturation factor 4)
*5
(Magnetic saturation factor 5)
*5
0: Motor characteristics 0 (Fuji standard IM, 8-series)
1: Motor characteristics 1 (HP rating IMs)
Slip compensation 2
(Operating conditions
0: Enable during acceleration/deceleration, enable at
base frequency or higher
1: Disable during acceleration/deceleration, enable at
base frequency or higher
2: Enable during acceleration/deceleration, disable at
base frequency or higher
3: Disable during acceleration/deceleration, disable at
Output current fluctuation
damping gain for motor 2
Speed control 2 *5
(Speed command filter)
0.001 to 9.999 s; 999 (Cancel integral term)
(Notch filter resonance
frequency)
(Notch filter attenuation level)
Cumulative motor run time 2
Change in cumulative motor run time (Reset is enabled)
Startup counter for motor 2
For adjustment at replacement
(0000 to FFFF in hexadecimal)
Motor 2
(%X correction factor 1)
(Torque current under vector
control) *5
(Induced voltage factor under
vector control) *5
(Data is displayed in decimal, Meaning of each bit 0:
Disable; 1 Enable)
bit0: Current limiter (F43, F44)
bit1: Rotational direction control (H08)
bit2: Non-linear V/f (H50 to H53, H65, H66)
bit3: PID control (J01 to J62, H91)
bit4: Brake signal
bit5: Braking timer at the Startup (H195)
Factory default
A (For Asia), C (for China), E (for Europe), U (For USA), J (for Japan), K (for Korea)
*5: Available at ROM version 0300 or later.
*6: Factory defaults are depended on motor capacity. Refer to “5.2.4 Motor constant”.
*9: Factory use. Do not change these function codes.