EasyManua.ls Logo

Fuji Electric FRENIC-Ace series - Page 192

Fuji Electric FRENIC-Ace series
788 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
5.2 Function Codes Table
5-22
Code
Name Data setting range
Change when running
Data copying
Factory
Default
Drive control
Related page
V/f
PG V/f
w/ PG
Torque control
PM
A23
Motor 2
(Slip compensation gain for
driving)
0.0 to 200.0%
Y*
Y
100.0
Y
Y
Y
N
N
A24
(Slip compensation response
time)
0.01 to 10.00 s
Y
Y1
Y2
0.50
Y
Y
N
N
N
A25
(Slip compensation gain for
braking)
0.0 to 200.0%
Y*
Y
100.0
Y
Y
Y
N
N
A26
(Rated slip frequency)
0.00 to 15.00Hz
N
Y1
Y2
*6
Y
Y
Y
N
N
A27
(Iron loss factor 1)
0.00 to 20.00%
Y
Y1
Y2
*6
Y
Y
Y
Y
N
A30
(Magnetic saturation factor 1)
*5
0.0 to 300.0 %
Y
Y1
Y2
*6
N
N
Y
Y
N
A31
(Magnetic saturation factor 2)
*5
0.0 to 300.0 %
Y
Y1
Y2
*6
N
N
Y
Y
N
A32
(Magnetic saturation factor 3)
*5
0.0 to 300.0 %
Y
Y1
Y2
*6
N
N
Y
Y
N
A33
(Magnetic saturation factor 4)
*5
0.0 to 300.0 %
Y
Y1
Y2
*6
N
N
Y
Y
N
A34
(Magnetic saturation factor 5)
*5
0.0 to 300.0 %
Y
Y1
Y2
*6
N
N
Y
Y
N
A39
Motor 2 selection
0: Motor characteristics 0 (Fuji standard IM, 8-series)
1: Motor characteristics 1 (HP rating IMs)
4: Other IMs
N
Y1
Y2
U:1
ACEJK:0
Y
Y
Y
Y
N
A40
Slip compensation 2
(Operating conditions
selection)
0: Enable during acceleration/deceleration, enable at
base frequency or higher
1: Disable during acceleration/deceleration, enable at
base frequency or higher
2: Enable during acceleration/deceleration, disable at
base frequency or higher
3: Disable during acceleration/deceleration, disable at
base frequency or higher
N
Y
0
Y
Y
N
N
N
A41
Output current fluctuation
damping gain for motor 2
0.00 to 1.00
Y
Y
0.20
Y
Y
N
N
N
A43
Speed control 2 *5
(Speed command filter)
0.000 to 5.000 s
Y
Y
0.020
N
Y
Y
N
Y
5-228
A44
(Speed detection filter)
0.000 to 0.100 s
Y*
Y
0.005
N
Y
Y
N
Y
A45
P (Gain)
0.1 to 200.0 times
Y*
Y
10.0
N
Y
Y
N
Y
A46
I (Integral time)
0.001 to 9.999 s; 999 (Cancel integral term)
Y
Y
0.100
N
Y
Y
N
Y
A47
FF (Gain)
0.00 to 99.99 s
Y
Y
0.00
N
N
Y
N
Y
A49
(Notch filter resonance
frequency)
1 to 200 Hz
Y
Y
200
N
N
Y
N
N
A50
(Notch filter attenuation level)
0 to 20 dB
Y
Y
0
N
N
Y
N
N
A51
Cumulative motor run time 2
0 to 9999
Change in cumulative motor run time (Reset is enabled)
(in units of 10 hours)
N
N
Y
Y
Y
Y
N
A52
Startup counter for motor 2
For adjustment at replacement
(0000 to FFFF in hexadecimal)
Y
N
Y
Y
Y
Y
N
A53
Motor 2
(%X correction factor 1)
0 to 300%
Y
Y1
Y2
100
Y
Y
Y
Y
N
A55
(Torque current under vector
control) *5
0.00 to 2000 A
N
Y1
Y2
*6
N
N
Y
Y
N
A56
(Induced voltage factor under
vector control) *5
50 to 100 %
N
Y1
Y2
*6
N
N
Y
Y
N
A98
Motor 2
(Function selection)
0 to 255
(Data is displayed in decimal, Meaning of each bit 0:
Disable; 1 Enable)
bit0: Current limiter (F43, F44)
bit1: Rotational direction control (H08)
bit2: Non-linear V/f (H50 to H53, H65, H66)
bit3: PID control (J01 to J62, H91)
bit4: Brake signal
bit5: Braking timer at the Startup (H195)
Bit6 to 7: Reserved *9
N
Y
0
Y
Y
Y
Y
Y
5-195
Factory default

A (For Asia), C (for China), E (for Europe), U (For USA), J (for Japan), K (for Korea)
*5: Available at ROM version 0300 or later.
*6: Factory defaults are depended on motor capacity. Refer to 5.2.4 Motor constant”.
*9: Factory use. Do not change these function codes.