5.2 Function Codes Table
5-23
FUNCTION CODES
Chap 5
b codes: Motor control parameter 3
Code
Name Data setting range
Change when running
Data copying
Factory
Default
Drive control
Related page
V/f
PG V/f
w/ PG
Torque control
PM
b43
Speed control 3 *5
(Speed command filter)
0.000 to 5.000 s
Y
Y
0.020
N
Y
Y
N
Y
5-228
b44
(Speed detection filter)
0.000 to 0.100 s
Y*
Y
0.005
N
Y
Y
N
Y
b45
P (Gain)
0.1 to 200.0
Y*
Y
10.0
N
Y
Y
N
Y
b46
I (Integral time)
0.001 to 9.999 s; 999 (Cancel integral term)
Y*
Y
0.100
N
Y
Y
N
Y
b47
FF (Gain)
0.00 to 99.99
Y*
Y
0.00
N
N
Y
N
Y
b49
(Notch filter resonance
frequency)
1 to 200Hz
Y
Y
200
N
N
Y
N
N
b50
(Notch filter attenuation level)
0 to 20dB
Y
Y
0
N
N
Y
N
N
*5: Available at ROM version 0300 or later.
r codes: Motor control parameter 4
Code
Name Data setting range
Change when running
Data copying
Factory
Default
Drive control
Related page
V/f
PG V/f
w/ PG
Torque control
PM
r43
Speed control 4 *5
(Speed command filter)
0.000 to 5.000 s
Y
Y
0.020
N
Y
Y
N
Y
5-228
r44
(Speed detection filter)
0.000 to 0.100 s
Y*
Y
0.005
N
Y
Y
N
Y
r45
P (Gain)
0.1 to 200.0 times
Y*
Y
10.0
N
Y
Y
N
Y
r46
I (Integral time)
0.001 to 9.999 s; 999 (Cancel integral term)
Y*
Y
0.100
N
Y
Y
N
Y
r47
FF (Gain)
0.00 to 99.99
Y*
Y
0.00
N
N
Y
N
Y
r49
(Notch filter resonance
frequency)
1 to 200 Hz
Y
Y
200
N
N
Y
N
N
r50
(Notch filter attenuation level)
0 to 20 dB
Y
Y
0
N
N
Y
N
N
*5: Available at ROM version 0300 or later.