5.2 Function Codes Table
5-29
FUNCTION CODES
Chap 5
U codes: Application Functions 3 (Customizable logic)
Code Name Data setting range
Change when running
Data copying
Factory
Default
Drive control
Related page
V/f
PG V/f
w/ PG
Torque control
PM
U00
Customizable logic
(Mode selection)
0: Disable
1: Enable (Customizable logic operation)
ECL alarm occurs when the value is changed from 1 to 0
during operation.
Y
Y
0
Y
Y
Y
Y
Y
5-250
U01
Customizable logic: Step 1
(Block selection)
[Digital]
0: No function assigned
10 to 15: Through output + General-purpose timer
20 to 25: Logical AND + General-purpose timer
30 to 35: Logical OR + General-purpose timer
40 to 45: Logical XOR + General-purpose timer
50 to 55: Set priority flip-flop + General-purpose timer
60 to 65: Reset priority flip-flop + General-purpose timer
70, 72, 73: Rising edge detector + General-purpose timer
80, 82, 83: Falling edge detector + General-purpose timer
90, 92, 93: Rising & falling edges detector +
General-purpose timer
100 to 105: Hold + General-purpose timer
110: Increment counter
120: Decrement counter
130: Timer with reset input
General-purpose timer function
(Least significant digit 0 to 5)
_0: No timer
_1: On-delay timer
_2: Off-delay timer
_3: Pulse (1 shot)
_4: Retriggerable timer
_5: Pulse train output
[Analog]
2001: Adder
2002: Subtracter
2003: Multiplier
2004: Divider
2005: Limiter
2006: Absolute value of input
2007: Inverting adder
2008: Variable limiter
2009: Linear function
2051 to 2056: Comparator1 to 6
2071, 2072: Window comparator1, 2
2101: High selector
2102: Low selector
2103: Average of inputs
2151: Loading function from S13
2201: Clip and map function
2202: Scale converter
3001: Quadratic function
3002: Square root function
[Digital, Analog]
4001: Hold
4002: Inverting adder with enable
4003, 4004: Selector 1, 2
4005: LPF(Low-pass filter) with enable
4006: Rate limiter with enable
5000: Selector 3
5100: Selector 4
6001: Reading function code
6002: Writing function code
6003: Temporary change of function code
6101: PID dancer output gain frequency
N
Y
0
Y
Y
Y
Y
Y