5.2 Function Codes Table
5-30
Code Name Data setting range
Change when running
Data copying
Factory
Default
Drive control
Related page
V/f
PG V/f
w/ PG
Torque control
PM
U02
Customizable logic: Step 1
(Input 1)
[Digital] 0 to 105: The same as E20 value. However, 27, 111
to 120 cannot be selected
N
Y
100
Y
Y
Y
Y
Y
U03
(Input 2)
2001 to 2200 (3001 to 3200): Output of Step 1 to 200
N
Y
100
Y
Y
Y
Y
Y
4001 (5001): X1 terminal input signal X1
4002 (5002): X2 terminal input signal X2
4003 (5003): X3 terminal input signal X3
4004 (5004): X4 terminal input signal X4
4005 (5005): X5 terminal input signal X5
4010 (5010): FWD terminal input signal FWD
4011 (5011): REV terminal input signal REV
*4021(5021): Digital input I1 (OPC-DIO) *5
*4022(5022): Digital input I2 (OPC-DIO) *5
*4023(5023): Digital input I3 (OPC-DIO) *5
*4024(5024): Digital input I4 (OPC-DIO) *5
*4025(5025): Digital input I5 (OPC-DIO) *5
*4026(5026): Digital input I6 (OPC-DIO) *5
*4027(5027): Digital input I7 (OPC-DIO) *5
*4028(5028): Digital input I8 (OPC-DIO) *5
*4029(5029): Digital input I9 (OPC-DIO) *5
*4030(5030): Digital input I10 (OPC-DIO) *5
*4031(5031): Digital input I11 (OPC-DIO) *5
*4032(5032): Digital input I12 (OPC-DIO) *5
*4033(5033): Digital input I13 (OPC-DIO) *5
6000 (7000): Final run command RUN FL_RUN
6001 (7001): Final run command FWD FL_FWD
6002 (7002): Final run command REV FL_REV
6003 (7003): Accelerating DACC
6004 (7004): Decelerating DDEC
6005 (7005): Under anti-regenerative control “REGA”
6006 (7006): Within dancer reference position DR_REF
6007 (7007): With/without alarm factor ALM_ACT
* Inside the ( ) is the negative logic signal. (OFF at
short-circuit)
[Analog]
8000 to 8021: The value with 8000 added to F31
9001: Analog 12 terminal input signal [12]
9002: Analog C1 terminal input signal [C1] (C1)
9003: Analog V2 terminal input signal [C1] (V2)
*9004: Analog 32 terminal input signal [32] *5
*9005: Analog C2 terminal input signal [C2] *5
U04
(Function 1)
-9990 to 0.00 to 9990
N
Y
0.00
Y
Y
Y
Y
Y
U05
(Function 2)
N
Y
0.00
Y
Y
Y
Y
Y
*: The use of the option card lets those functions remain in effect.
*5: Available at ROM version 0300 or later.
Customizable logic Step 1 to 14 function code is assigned as follows: Setting value is the same as U01 to U05.
Step1
Step2
Step3
Step4
Step5
Step6
Step7
Step8
Step9
Step10
Block selection
U01
U06
U11
U16
U21
U26
U31
U36
U41
U46
Input 1
U02
U07
U12
U17
U22
U27
U32
U37
U42
U47
Input 2
U03
U08
U13
U18
U23
U28
U33
U38
U43
U48
Function 1
U04
U09
U14
U19
U24
U29
U34
U39
U44
U49
Function 2
U05
U10
U15
U20
U25
U30
U35
U40
U45
U50
Step11
Step12
Step13
Step14
Block selection
U51
U56
U61
U66
Input 1
U52
U57
U62
U67
Input 2
U53
U58
U63
U68
Function 1
U54
U59
U64
U69
Function 2
U55
U60
U65
U70

Table of Contents