5.2 Function Codes Table
5-33
FUNCTION CODES
Chap 5
y codes: LINK Functions (Link function)
Code
Name Data setting range
Change when running
Data copying
Factory
Default
Drive control
Related page
V/f
PG V/f
w/ PG
Torque control
PM
y01
RS-485 Communication 1
(Station address)
1 to 255
N
Y
1
Y
Y
Y
Y
Y
5-277
y02
(Communications error
processing)
0: Immediately trip with alarm
er8
1: Trip with alarm
er8
after running for the period
specified by timer y03
2: Retry during the period specified by timer y03. If the
retry fails, trip with alarm
er8
. If it succeeds, continue
to run.
3: Continue to run
Y
Y
0
Y
Y
Y
Y
Y
y03
(Timer)
0.0 to 60.0 s
Y
Y
2.0
Y
Y
Y
Y
Y
y04
(Baud rate)
0: 2400 bps
1: 4800 bps
2: 9600 bps
3: 19200 bps
4: 38400 bps
Y
Y
3
Y
Y
Y
Y
Y
y05
(Data length selection)
0: 8 bit 1: 7 bits
Y
Y
0
Y
Y
Y
Y
Y
y06
(Parity selection)
0: None (Stop bit: 2 bits)
1: Even number parity (Stop bit: 1 bits)
2: Odd number parity (Stop bit: 1 bits)
3: None (Stop bit: 1 bits)
Y
Y
0
Y
Y
Y
Y
Y
y07
(Stop bit selection)
0: 2 bits 1: 1 bits
Y
Y
0
Y
Y
Y
Y
Y
y08
(Communication time-out
detection timer)
0: Not check of the time-out
1 to 60 s
Y
Y
0
Y
Y
Y
Y
Y
y09
(Response interval time)
0.00 to 1.00 s
Y
Y
0.01
Y
Y
Y
Y
Y
y10
(Protocol selection)
0: Modbus RTU protocol
1: FRENIC Loader protocol (SX protocol)
2: Fuji general-purpose inverter protocol
Y
Y
1
Y
Y
Y
Y
Y
y11
RS-485 Communication 2
(Station address)
1 to 255
N
Y
1
Y
Y
Y
Y
Y
y12
(Communications error
processing)
0: Immediately trip with alarm
erp
1: Trip with alarm
erp
after running for the period
specified by timer y13
2: Retry during the period specified by timer y13. If the
retry fails, trip with alarm
erp
. If it succeeds, continue
to run.
3: Continue to run
Y
Y
0
Y
Y
Y
Y
Y
y13
(Timer)
0.0 to 60.0 s
Y
Y
2.0
Y
Y
Y
Y
Y
y14
(Baud rate)
0: 2400 bps
1: 4800 bps
2: 9600 bps
3: 19200 bps
4: 38400 bps
Y
Y
3
Y
Y
Y
Y
Y
y15
(Data length selection)
0: 8 bits 1: 7 bits
Y
Y
0
Y
Y
Y
Y
Y
y16
(Parity selection)
0: None (Stop bit: 2 bits)
1: Even number parity (Stop bit: 1 bits)
2: Odd number parity (Stop bit: 1 bits)
3: None (Stop bit: 1 bits)
Y
Y
0
Y
Y
Y
Y
Y
y17
(Stop bit selection)
0: 2 bits 1: 1 bit
Y
Y
0
Y
Y
Y
Y
Y
y18
(Communication time-out
detection timer)
0: Not check of the time-out
1 to 60 s
Y
Y
0
Y
Y
Y
Y
Y
y19
(Response interval time)
0.00 to 1.00 s
Y
Y
0.01
Y
Y
Y
Y
Y
y20
(Protocol selection)
0: Modbus RTU protocol
1: FRENIC Loader protocol (SX protocol)
2: Fuji general-purpose inverter protocol
Y
Y
0
Y
Y
Y
Y
Y