5.2 Function Codes Table
5-34
Code
Name Data setting range
Change when running
Data copying
Factory
Default
Drive control
Related page
V/f
PG V/f
w/ PG
Torque control
PM
y21
Built-in CAN communication
(Node ID)
1 to 127
N
Y
1
Y
Y
Y
Y
Y
5-280
y24
(Baud rate)
0: 125kbps
1: 20kbit/s
2: 50kbit/s
3: 125kbit/s
4: 250kbit/s
5: 500kbit/s
6: 800kbit/s
7: 1Mbit/s
N
Y
0
Y
Y
Y
Y
Y
y25
Map the inverter function
code1 to RPDO No. 3
0000 to FFFF (in hexadecimal)
N
Y
0000
Y
Y
Y
Y
Y
y26
Map the inverter function
code2 to RPDO No. 3
Data mapped I/O (Write)
Y
Y
Y
Y
Y
y27
Map the inverter function
code3 to RPDO No. 3
Y
Y
Y
Y
Y
y28
Map the inverter function
code4 to RPDO No. 3
Y
Y
Y
Y
Y
y29
Map the inverter function
code1 to TPDO No. 3
Y
Y
Y
Y
Y
y30
Map the inverter function
code2 to TPDO No. 3
Y
Y
Y
Y
Y
y31
Map the inverter function
code3 to TPDO No. 3
Y
Y
Y
Y
Y
y32
Map the inverter function
code4 to TPDO No. 3
Y
Y
Y
Y
Y
y33
(Operation selection)
0: Disable, 1: Enable
Y
Y
0
Y
Y
Y
Y
Y
y34
(Communications error
processing)
This function code is valid in case of y36=-4 or -5.
1:
After the time specified by [y35], coast to a stop and trip
with [ert].
2: If the
inverter receives any data within the time specified
by [y35], ignore the communications error. After the
timeout, coast to a stop and trip with [ert].
10: Immediately decelerate to a stop. Issue [ert] after
stopping.
11: After the time specified by [y35], decelerate to a stop.
Issue [ert] after stopping.
12:
If the inverter receives any data within the time specified
by [y35], ignore the communications error. After the
timeout, decelerate to a stop and trip with [ert].
Otherwise: Immediately coast to a stop and trip with [ert].
Y
Y
0
Y
Y
Y
Y
Y
y35
(Communication time-out
detection timer)
0.0 to 60.0
Y
Y
0.0
Y
Y
Y
Y
Y
y36
(Operation selection in abort
status) *5
-5 to 3
Y
Y
1
Y
Y
Y
Y
Y
y95
Data clear processing for
communications error
0: Do not clear the data of function codes Sxx when a
communications error occurs. (compatible with the
conventional inverters)
1: Clear the data of function codes S01/S05/S19 when a
communications error occurs.
2: Clear the run command assigned bit of function code
S06 when a communications error occurs.
3: Clear both data of S01/S05/S19 and run command
assigned bit of S06 when a communications error
occurs.
* Related alarms:
er8
,
erp
,
er4
,
er5
,
ert
Y
Y
0
Y
Y
Y
Y
Y
5-280
y97
Communication data storage
selection
0: Store into nonvolatile memory (Rewritable times are
limited)
1: Write into temporary memory (Rewritable times are
unlimited)
2: Save all data from temporary memory to nonvolatile
memory (After all save, return to Data 1)
Y
Y
0
Y
Y
Y
Y
Y
5-280
y98
Bus link function
(Mode selection)
Frequency command Run command
0: Follow H30 Follow H30
1: Bus link Follow H30
2: Follow H30 Bus link
3: Bus link Bus link
Y
Y
0
Y
Y
Y
Y
Y
5-280
y99
Loader link function
(Mode selection)
Frequency command Run command
0: Follow H30, y98 Follow H30, y98
1: FRENIC loader Follow H30, y98
2: Follow H30, y98 FRENIC loader
3: FRENIC loader FRENIC loader
Y
N
0
Y
Y
Y
Y
Y
5-281
*5: Available at ROM version 0300 or later.

Table of Contents