5.3 Description of Function Codes
5-82
■ Output gain (F30, F34)
F30, F34 allows you to adjust the output voltage within the range of 0 to 300%.
■ Function selection (F31, F35)
F31, F35 specify which data is monitored at the output terminals [FM], [FM2].
F31/F35
data
[FMA] output Data Definition of monitor amount 100%
0
Output frequency 1
(before slip
compensation)
Output frequency of the inverter
(Equivalent to the motor
synchronous speed)
Maximum frequency (F03)
1
Output frequency 2
(after slip
compensation)
Output frequency of the inverter Maximum frequency (F03)
2 Output current Output current (RMS) of the inverter
Twice the inverter rated current
(Inverter rated output current
depending on F80 setting)
3 Output voltage Output voltage (RMS) of the inverter
200 V class: 250 V
400 V class: 500 V
4 Output torque Motor shaft torque Twice the rated motor torque
5 Load factor
Load factor (Equivalent to the
indication of the load meter)
Twice the rated motor load
6 Input power Input power of the inverter
Twice the rated output power
(Inverter rated output power
depending on F80)
7 PID feedback value Feedback value under PID control 100% of the feedback amount
8
Actual speed/
estimated speed
Speed detected through the PG
interface, or estimated speed under
vector control without speed sensor
Maximum speed as 100%
9 DC link bus voltage DC link bus voltage of the inverter
200 V class: 500 V
400 V class: 1000 V
10 Universal AO
Command from communication
( RS-485 communication user
manual)
20,000/100%
13 Motor output Motor output (kW)
Twice the rated motor output
(P02/A16 setting value)
14 Calibration (+)
For meter calibration
Full scale output
Always full scale (equivalent to
100%)
Output
15 PID command (SV) Command value under PID control PID command 100%
16 PID output (MV)
Output level of the PID processor
under PID control (Frequency
command)
Maximum frequency (F03)