5.3 Description of Function Codes
5-144
C31 to C35
C36 to C40
C41 to C45
Analog input adjustment (terminal [12])
(offset, gain, filter time constant, gain base point, polarity)
Analog input adjustment (terminal [C1] C1 function)
(offset, gain, filter time constant, gain base point, range/polarity)
Analog input adjustment (terminal [C1] V2 function)
(offset, gain, filter time constant, gain base point, polarity)
(refer to F01 for frequency setting)
C55, C56
C61, C62
C67, C68
Bias (for PID, frequency command 2 (terminal [12])) (bias, bias base point) (refer to F01)
Bias (for PID, frequency command 2 (terminal [C1]) (C1 function))
(bias, bias base point)(refer to F01)
Bias (for PID, frequency command 2 (terminal [C1]) (V2 function))
(bias, bias base point)(refer to F01)
You can adjust the gain, bias, polarity, filter time constant and offset which are applied to analog inputs (voltage
inputs to terminals [12] and [C1] (V2 function) and current input to terminal [C1] (C1 function)).
Adjustable items for analog inputs (excluding those for frequency command 1)
Input
terminal
Input range
Bias Gain
Polarity
constant
Offset
Bias Base point
Gain Base point
[12] 0 to +10 V, -10 to +10 V
C55 C56 C32 C34 C35 C33 C31
[C1] (C1) 4 to 20 mA, 0 to 20 mA
C61 C62 C37 C39 C40 C38 C36
[C1] (V2) 0 to +10 V C67 C68 C42 C44 C45 C43 C41
■ Offset (C31, C36, C41)
C31, C36 or C41 configures an offset for an analog voltage/current input.
• Data setting range: -5.0 to +5.0 (%)
■ Filter time constant (C33, C38, C43)
C33, C38, and C43 provide the filter time constants for the voltage and current of the analog input. The larger the
time constant, the slower the response. Specify the proper filter time constant taking into account the response
speed of the machine (load). If the input voltage fluctuates due to line noises, increase the time constant.
• Data setting range: 0.00 to 5.00 (s)
■ Polarity Terminal [12] (C35)
C35 and C45 configure the input range for analog input voltage.
C35 data Modes for terminal inputs
0 -10 to +10 V
1 0 to +10 V (negative value of voltage is regarded as 0 V)
■ Polarity [C1] (V2 function) (C45)
C45 data Modes for terminal inputs
0 0 to +10 V
When the bias is specified to be a negative value, makes a point lower than 0
effective as a negative value.
1 0 to +10 V (factory default)
When the bias is specified to be a negative value, limits a point lower than 0 to 0.