5.3 Description of Function Codes
5-145
FUNCTION CODES
Chap 5
Gain
To input bipolar analog voltage (0 to ±10 VDC) to terminal [12], set C35 data to 0.Setting C35 data to
1” enables only the voltage range from 0 to +10 VDC and interprets the negative
polarity input from 0 to
-
10 VDC as 0 V.
Terminal [C1] (C1 function) range / polarity selection(C40)
Selects the range of current input terminal [C1](C1 function).
C40 data Terminal input range When specified bias is negative
0 4 to 20 mA (factory default)
Limits a point lower than 0 to 0.
1 0 to 20 mA
10 4 to 20 mA
Makes a point lower than 0 effective as a negative
value.
11 0 to 20mA
For using terminal [C1] for the C1, V2 or PTC function, it is necessary to make the settings as shown below.
Terminal [C1] SW3 SW4 E59 H26 C40
For use of C1 function (4 to 20 mA) C1 AI 0 0 0, 10
For use of C1 function (0 to 20 mA) C1 AI 0 0 1, 11
For use of V2 function (0 to +10V)
V2 AI 1 0
Does not
matter
For use of PTC function
C1 PTC
Does not
matter
1, 2
Does not
matter
For details about SW3 and SW4, refer to Chapter 2, Section 2.2.8.
Expected operation may not be obtained if the settings above are not switched correctly. Use sufficient caution.
Reference frequency
Gain
Gain base
point
Analog input
Point
X