5.3 Description of Function Codes
5-161
FUNCTION CODES
Chap 5
H11
Deceleration mode
H11 specifies the deceleration mode to be applied when a run command is turned OFF.
H11 data Action
0 Normal deceleration
1 The inverter immediately shuts down its output, so the motor stops according to the
inertia of the motor and machinery (load) and their kinetic energy losses.
When reducing the reference frequency, the inverter decelerates the motor according to the deceleration
commands even if H11 = 1 (Coast
Instantaneous overcurrent limiting (Mode selection) (refer to F43)
Refer to the descriptions of F43 and F44.
H13, H14
H15, H16
Restart mode after momentary power failure (Restart time, frequency fall rate)
Restart mode after momentary power failure (Continue to run level, allowable
momentary power failure time) (refer to F14)
For how to set these function codes (Restart time, Frequency fall rate, Continue to run level and Allowable
momentary power failure time), refer to the description of F14.