5.3 Description of Function Codes
5-270
■ Function codes for the customizable logic
Function code
number
Name Range Minimum unit Remarks
U121 to U140 User parameter 1 to 20 -9990.00 to 9990.00
Effective number are 3 digits.
0.01 to 10
U171 to U175 Storage area 1 to 5 -9990.00 to 9990.00
Effective number are 3 digits.
0.01 to 10 Memorize the data
when powered off.
■ Configuration of function codes
Set a function code group (code from the following table) to function 1 (such as U04) and set the last two digits of
the function code number to function 2 (such as U05) to specify individual function codes.
Group Code Name Group Code Name
F 0 00
H
Basic function
U1 39 27
H
For customizable logic
E 1 01
H
Terminal function
y 14 0E
H
Link function
C 2 02
H
Control function
K 28 1A
H
Touch panel function
P 3 03
H
Motor1
M 8 08
H
Monitor data
H 4 04
H
High performance function
o 6 06
H
Option function
H1 31 1F
H
High performance function 1
d 19 13
H
Applied function 2
A 5 05
H
Speed control 2
U 11 0B
H
Customizable logic
b 18 12
H
Speed control 3
W 15 0F
H
Monitor 2
r 10 0A
H
Speed control 4
X 16 10
H
Alarm 1
J 13 0D
H
Applied function 1
Z 17 11
H
Alarm 2
J1 48 30
H
Applied function 1
■ Task process cycle setting (U100)
U100 data Data
0 Automatically adjusts the task cycle from 2 ms to 10 ms depending on the number of used
steps. This is the factory default. It is recommended to use this value.
2 2 ms: Up to 10 steps. If it exceeds 10 steps, the customizable logic does not work.
5 5 ms: Up to 50 steps. If it exceeds 50 steps, the customizable logic does not work.
10 10 ms: Up to 100 steps. If it exceeds 100 steps, the customizable logic does not work.
20 20 ms Up to 200 steps.
Note that if it exceeds the steps defined in 2, 5 or 10, the customizable logic does not work.