5.3 Description of Function Codes
5-275
FUNCTION CODES
Chap 5
Setting example 2: Bring multiple output signals in a single signal
If the general-purpose RUN signal is kept ON at restart after momentary power failure, replace an external circuit
that is conventionally needed with a customizable logic sequence to reduce the general-purpose output terminals
and external relays.
To configure this customizable logic, set the function codes as follows. (Timer selection) and (Timer setting) do not
need to be modified if no change is made.
Function code
value
Settings Remarks
E20 Terminal [Y1] function 111 Customizable logic output
signal 1 “CL01”
U00 Customizable Logic (Mode selection) 1 Enable
U01 Customizable logic:
Step 1
(Block
selection)
30 Logical OR +
General-purpose timer
Mode selection
U02 (Input 1) 0 During operation “RUN”
U03 (Input 2) 6 Auto-restarting after
momentary power failure “IPF”
U71 Customizable logic
output signal 1
(Output
selection)
1 Output of step 1, “SO01”
U81 (Function
selection)
100 No function assigned “NONE”