5.3 Description of Function Codes
5-276
Setting example 3: One-shot operation
The required operation is as follows: SW-FWD or SW-REV switch is short-circuited to start the operation and the
SW-STOP switch is short-circuited to stop the operation (equivalent to / keys/ key on keypad), if the
above operation is required, replace an external circuit that is conventionally needed with customizable the
customized logic.
To configure this customizable logic, set the function codes as follows. (Timer selection) and (Timer setting) do not
need to be modified if no change is made.
Function code
Setting
value
Settings Remarks
F02 Operation method 1 External signal
E01 Terminal [X1] function 100 No function assigned “NONE
E98 Terminal [FWD] function 100 No function assigned “NONE
E99 Terminal [REV] function 100 No function assigned “NONE
U00 Customizable Logic (Mode selection) 1 Enable
U01 Customizable logic:
Step 1
(Block selection) 30 Logical OR + General-purpose timer Mode selection
U02 (Input 1) 4011 Terminal REV input signal “SW-REV”
U03 (Input 2) 4001 Terminal X1 input signal “SW-STOP
U06 Customizable logic:
Step 2
(Block selection) 60 Reset priority flip-flop + General-purpose timer Mode selection
U07 (Input 1) 4010 Terminal FWD input signal “SW-FWD
U08 (Input 2) 2001 Output of step 1 “SO01
U11 Customizable logic:
Step 3
(Block selection) 30 Logical OR + General-purpose timer Mode selection
U12 (Input 1) 4010 Terminal FWD input signal “SW-FWD
U13 (Input 2) 4001 Terminal X1 input signal “SW-STOP
U16 Customizable logic:
Step 4
(Block selection) 60 Reset priority flip-flop + General-purpose timer Mode selection
U17 (Input 1) 4011 Terminal REV input signal “SW-REV”
U18 (Input 2) 2003 Output of step 3 “SO03
U71 Customizable logic
output signal 1
(Output selection) 2 Output of step 2 “SO02 FWD
command
U72 Customizable logic
output signal 2
4 Output of step 4 SO04 “REV”
command
U81 Customizable logic
output signal 1
(Function
selection)
98 Run forward/stop command “FWD
U82 Customizable logic
output signal 2
99 Run reverse/stop command “REV”