12.1 Standard Model
12-15
SPECIFICATIONS
Chap 12
■ Standard-model, Three-phase 400 V (460 V) class series (HHD-mode: 5.5 kW to 37 kW)
Item Specifications
Type (FRN_ _ _ _E2S-4) 0022 0029 0037 0044 0059 0072 0085 0105
Nominal applied motor (kW) [HP]
(Output rating)
5.5
[7.5]
7.5
[10]
11
[15]
15
[20]
18.5
[25]
22
[30]
30
[40]
37
[50]
Output ratings
Rated capacity (kVA) *2
9.9
[10]
14
[14]
18
[19]
23
[24]
30
[31]
34
[36]
46
[48]
57
[60]
Rated voltage (V) *
Three-phase 380 to 480 V (with AVR function)
Rated current (A) *4 13 18 24 30 39 45 60 75
Overload capability 150%-1 min, 200%-0.5 s
Input power
Voltage, frequency Three-phase 380 to 480 V, 50/60 Hz
Allowable voltage/frequency
Voltage: +10 to -15% (Interphase voltage unbalance: 2% or less) *6,
Frequency: +5 to -5%
Rated input current *7
(w/o DCR) (A)
17.3 23.2 33 43.8 52.3 60.6 77.9 94.3
(with DCR) (A) 10.6 14.4 21.1 28.8 35.5 42.2 57.0 68.5
Required capacity
(with DCR) (kVA) *8
7.3 10 15 20 25 29 39 47
Braking
Torque (%)
20% 10% to 15%
DC braking
Braking starting frequency: 0.0 to 60.0 Hz, Braking time: 0.0 to 30.0 s,
Braking level: 0 to 100%
Braking transistor Built-in as standard
Minimum resistance value (Ω)
80 60 40 34.4 16
-
Braking resistor Separately mounted option
DC reactor (DCR) Separately mounted option
Applicable safety standards IEC/EN61800-5-1: 2007
Enclosure (IEC60529) IP20, UL open type
Cooling method Fan cooling
Weight / Mass (kg) [lbs]
5.0
[11]
5.0
[11]
8.0
[18]
9.0
[20]
9.5
[21]
10
[22]
25
[55]
26
[57]
Note: A box () in the above table replaces GA, GB or C depending on the model.
*1 Fuji 4-pole standard motor
*2 Rated capacity is calculated assuming the rated output voltage as 440 V (460 V).
*3 Output voltage cannot exceed the power supply voltage.
*4 Setting the carrier frequency (F26) to the following value or above requires current derating.
HHD spec of type FRN0002E2■-4 to FRN0012E2■-4: 8 kHz,
HHD spec of type FRN0022E2■-4 to FRN0168E2■-4: 10 kHz,
HHD spec of type FRN0203E2■-4 to FRN0590E2■-4: 6 kHz,
If reduction is necessary, for details, refer to Figure 10.4-1 in Chapter 10 “10.4.2 Guideline for selecting
inverter drive mode and capacity.”
*6
67 ×
(V) voltage average phase-Three
(V) voltage Min. - (V) voltage Max.
=(%) unbalance Voltage
(IEC 61800-3)
If the unbalance ratio is 2% to 3%, use an optional AC reactor (ACR).
*7 This specification is an estimated value to be applied when the power supply capacity is 500 kVA (Inverter
capacity × 10 when the capacity exceeds 50 kVA) and the power supply with %X = 5% is connected. When
applying with motors of 75 kW (100 HP) or above, a DC reactor (DCR) should be used.
*8 This specification applies when a DC reactor (DCR) is used.
*9 Average braking torque for the motor running alone. It depends on the efficiency of the motor.