2.2 Wiring
2-48
Table 2.2-30 Functional Description of Control Circuit Terminals (continued)
Classification
Terminal
symbol
Terminal name Functional description
Transistor outputs
[Y1] Transistor
output 1
(1) Various signals (running signal, frequency reached signal, overload forecast signal, etc)
set up by function code E20, E21 can be output. For details, refer to Chapter 5
“FUNCTION CODE”.
(2) The operating mode of the transistor output terminals [Y1], [Y2] can be switched to “ON
(active ON) at signal output” or “OFF (active OFF) at signal output”.
<Transistor output circuit specification>
Photo coupler
<Control circuit block>
Y1 to
Y2
CMY
31 to 35V
Voltage
Current
Figure 2.2-18 Transistor Output Circuit
Connect a surge absorbing diode between the terminals the excitation coil
when connecting control relays.
When a power source is needed for the circuit to be connected, terminal PLC
can be used as a power source terminal. Rated voltage: DC+24 V (power
supply voltage fluctuation range: DC+22 to +27 V), maximum 50 mA). In this
case, terminal [CMY] must be shorted to terminal [CM].
[Y2] Transistor
output 2
[CMY] Transistor
output common
This terminal is the common terminal for transistor output signals.
This terminal is insulated from terminals [CM] and [11].
When connecting the programmable controller to terminals [Y1], [Y2].
The circuit configuration example for connecting the inverter transistor output to the programmable controller is
shown in Figure 2.2-19. Circuit (a) in Figure 2.2-19 shows the programmable controller input circuit as sink
input and circuit (b) shows as the source input case.
C0
DC+24 V
Programmable
controller
Sink type input
Photo coupler
<Control circuit block>
Y1,
Y2
CMY
31 to
35 V
Current
C0
Programmable
controller
Source type
input
DC+24 V
Photo coupler
<Control circuit block>
Y1 to
Y2
CMY
31 to
35 V
Current
(a) Connection diagram for sink input type
programmable controller
(b) Connection diagram for source input type
programmable controller
Figure 2.2-19 Example of Connection Circuit Configuration with Programmable Controller
Contact output
[30A/B/C] Integrated
alarm output
(1) When the inverter stops with an alarm, output is generated on the relay contact (1C).
Contact rating: AC250 V 0.3 A cos
φ
= 0.3, DC48 V 0.5 A
(2) Terminals can be switched to “Terminals [30A to 30C] shorted (excitation: active ON) at
ON signal output” or “Terminals [30A to 30C] open (non-excitation: active OFF) at ON
signal output”
Item Maximum
Operating
voltage
ON level 3 V
OFF level 27 V
Max load current at ON 50 mA
Leak current at OFF 0.1 mA