GAMATRONIC ELECTRONIC INDUSTRIES LTD.
+
SA: 20, 30 and 40 kVA, Release 2.1
95
2. Select Set absolute minimum output voltage:
[Main Menu > SETUP > (password) > Battery > Temp. Compensat. > Set
ABSOLUTE Max & Min Voltages]
1> Set absolute minimum output voltage
2> Set absolute maximum output voltage
--== Active in floating mode only ==--
Please select. 1
Figure 175: Select Set absolute minimum output voltage
3. Using the arrow keys, set the absolute minimum voltage when compensating and
then press Ent:
[Main Menu > SETUP > (password) > Battery > Temp. Compensat. > Set
ABSOLUTE Max & Min Voltages > Absolute MINimum Voltage While Cmpensat.]
Absolute minimum voltage while cmpensat.
Voltage setting: 720.0V
Figure 176: Set absolute minimum output voltage when compensating
4. Select Set absolute maximum output voltage:
[Main Menu > SETUP > (password) > Battery > Temp. Compensat. > Set
ABSOLUTE Max & Min Voltages]
1> Set absolute minimum output voltage
2> Set absolute maximum output voltage
--== Active in floating mode only ==--
Please select. 1
Figure 177: Select Set absolute maximum output voltage
5. Using the arrow keys, set the absolute maximum voltage when compensating, press
Ent, and then Esc:
[Main Menu > SETUP > (password) > Battery > Temp. Compensat. > Set
ABSOLUTE Max & Min Voltages > Absolute MAXimum Voltage While Cmpensat.]
Absolute maximum voltage while cmpensat.
Voltage setting: 870.0V
Figure 178: Set absolute maximum output voltage when compensating