9.12.3.2 Total Number of UPSs
1. Select # OF UPSs (total):
[Main Menu > SETUP > (password) > Ent > Service > Configure]
1> # OF UPSs (redundancy) 5> Dry, Alarms
2> # OF UPSs (total) 6> Calibration
3> # OF BATT 7> Parallel/StandAlone
4> Static Switch Setup 8> REM COMMAND
Figure 217: Service > Configure menu
2. Use the arrow keys to set the total number of UPSs and then press Ent:
[Main Menu > SETUP > (password) > Ent > Service > Configure > # OF UPSs
(total)]
Set number of UPSs (total)
04 (02 redundant)
Figure 218: Set total number of UPSs
9.12.3.3 Total Number of Batteries
1. Select # OF BATT:
[Main Menu > SETUP > (password) > Ent > Service > Configure]
1> # OF UPSs (redundancy) 5> Dry, Alarms
2> # OF UPSs (total) 6> Calibration
3> # OF BATT 7> Parallel/StandAlone
4> Static Switch Setup 8> REM COMMAND
Figure 219: Service > Configure menu
2. Use the arrow keys to set the total number of batteries and then press Ent:
[Main Menu > SETUP > (password) > Ent > Service > Configure > # OF BATT]
Set Number Of Batteries (0 to 3)
02
Figure 220: Set total number of batteries