GAMATRONIC ELECTRONIC INDUSTRIES LTD.
POWER
+
SA: 20, 30 and 40 kVA, Release 2.1
113
5. Press Ent to continue:
[Main Menu > SETUP > (password) > Ent > Service > Configure > Calibration > DC-
I Calibration]
1> Calibrate Battery #1 Current
Figure 233: Calibrating DC current
6. Using the arrow keys, set the actual current and then press Ent:
[Main Menu > SETUP > (password) > Ent > Service > Configure > Calibration > DC-
I Calibration > Ent]
CURRENT METER #01 CALIBRATION
Enter the value of the actual current:
02000 (X0.1)A
Figure 234: Entering actual current
9.12.3.7 Selecting Standalone or Parallel Operation
1. Select Parallel/StandAlone:
[Main Menu > SETUP > (password) > Ent > Service > Configure]
1> # OF UPSs (redundancy) 5> Dry, Alarms
2> # OF UPSs (total) 6> Calibration
3> # OF BATT 7> Parallel/StandAlone
4> Static Switch Setup 8> REM COMMAND
Figure 235: Service > Configure menu
2. Select Stand Alone or Parallel by using the ▲▼arrow keys and Ent:
[Main Menu > SETUP > (password) > Ent > Service > Configure >
Parallel/StandAlone]
--- Parallel / Stand-Alone Setup ---
SELECT - 1: Stand Alone (selected)
SELECT - 2: Parallel
Figure 236: Setting standalone or parallel operation