SA: 20, 30, and 40 kVA, Release 2.1
9.12.3.4 Setting up the Static Switch
1. Select Static Switch Setup:
[Main Menu > SETUP > (password) > Ent > Service > Configure]
1> # OF UPSs (redundancy) 5> Dry, Alarms
2> # OF UPSs (total) 6> Calibration
3> # OF BATT 7> Parallel/StandAlone
4> Static Switch Setup 8> REM COMMAND
Figure 221: Service > Configure menu
2. Select Set mask:
[Main Menu > SETUP > (password) > Ent > Service > Configure > Static Switch
Setup]
1. Set mask
2. Configure BYPASS
Figure 222: Static Switch setup menu
3. Use arrow keys to set the mask, and then press Ent:
[Main Menu > SETUP > (password) > Ent > Service > Configure > Static Switch
Setup > Set mask]
Figure 223: Set the mask
4. Select Configure BYPASS:
[Main Menu > SETUP > (password) > Ent > Service > Configure > Static Switch
Setup]
1. Set mask
2. Configure BYPASS
Figure 224: Static Switch setup menu