EasyManua.ls Logo

Gamatronic power+ sa - Self-Test Option; Figure 94: Main Menu Option 3 (Self Test); Figure 95: Result Screen from Self-Test

Gamatronic power+ sa
174 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
GAMATRONIC ELECTRONIC INDUSTRIES LTD.
POWER
+
SA: 20, 30 and 40 kVA, Release 2.1
65
9.4 “Self-test” Option
You can run a self-test at any time without interfering in the normal operation of the
POWER
+
. A self-test is also initiated by the POWER
+
itself each day at midnight.
Figure 94: Main Menu option 3 (“Self Test”)
The failure of a self-test sets on the self-test alarm. The self-test alarm can only be cleared
by a subsequent successful self-test, or it can be cleared manually by a maintenance
technician. Powering the POWER
+
down and up, for example, does not clear the self-test
alarm. This is because the failure of a self-test is considered a serious event that should not
be “forgotten”. A self-test failure is also recorded in the alarm log.
[Main Menu > SELFTEST]
Wait for results…
STATIC RAM: PASSED R.T CLOCK: PASSED
EEPROM – 1: PASSED
EEPROM – 3: PASSED DC SUPPLIES: PASSED
Figure 95: Result screen from self-test