GAMATRONIC ELECTRONIC INDUSTRIES LTD.
100
+
SA: 20, 30, and 40 kVA, Release 2.1
2. Select ENABLE SHUTDOWN by long AC FAIL (Off) and press Ent to toggle
enable/disable:
[Main Menu > SETUP > (password) > Battery > Enable/Dis Options]
1> ENABLE SHUTDOWN by long AC FAIL (Off)
2> ENABLE Current Sensors (Off)
3> ENABLE BATT Temperature sensor (Off)
Select & Press To toggle Enable/Disable
1> DISABLE SHUTDOWN by long AC FAIL(On )
2> ENABLE Current Sensors (Off)
3> ENABLE BATT Temperature sensor (Off)
Select & Press To toggle Enable/Disable
Figure 194: Enable/Disable shutdown by long AC failure
Note: Option 1 in Figure 194 allows the user to enforce shutdown after a given length of
input ac failure, even when the batteries are still fully charged.
Item 2, ENABLE Current Sensors (Off) and item 3, ENABLE BATT Temperature
sensor (Off) in the screens shown in Figure 194 toggle between enable/disable in
the same manner as item 1, ENABLE SHUTDOWN by long AC FAIL (Off).