GAMATRONIC ELECTRONIC INDUSTRIES LTD.
+
SA: 20, 30 and 40 kVA, Release 2.1
39
5. Select Configure, option 5, to configure the Power+ SA modules:
[Main Menu > SETUP > (password) > Ent > Service]
1> ------ 4> DryOut Test 7> --------
2> UPSs 5> Configure 8> Powr.Calib
3> ------- 6> En/Dis shar 9> SC2012..
Select, then Enter
Figure 36: Service menu
6. Select # UPSs (total), option 2, to specify the total number of modules in the
system:
[Main Menu > SETUP > (password) > Ent > Service > Configure]
1> # OF UPSs (redundancy) 5> Dry, Alarms
2> # OF UPSs (total) 6> Calibration
3> # OF BATT 7> Parallel/StandAlone
4> Static Switch Setup 8> REM COMMAND
Figure 37: Configure menu
7. Use the arrow keys to specify the total number of modules installed in the
Power+ SA, and then press Ent:
[Main Menu > SETUP > (password) > Ent > Service > Configure > # OF UPSs (total)]
Set number of UPSs (total)
04 (02 redundant)
Figure 38: # of UPSs (Total)
8. Select 1, # of UPSs (Redundancy) in Figure 37 to specify the number of modules
used for redundancy:
[Main Menu > SETUP > (password) > Ent > Service > Configure > # OF UPSs (redundancy)]
Set number of UPSs (Redundancy)
01 (04 total)
Figure 39: # of UPSs (Redundancy)
Note: The redundant modules are designated to replace other system modules when they
stop working. For example, a 40-kVA system with 4 modules of which two are
configured for redundancy can deliver a maximum of 20 kVA.