GAMATRONIC ELECTRONIC INDUSTRIES LTD.
POWER
+
SA: 20, 30 and 40 kVA, Release 2.1
35
6.5.3 Emergency Power-off
An external Emergency Power-Off (EPO) switch can be installed by the customer to enable
immediate shutdown of the UPS. Once switched off by the EPO, the POWER+ must be
restarted manually.
The UPS has two terminals marked "EPO" for connection of an EPO switch (Figure 27).
Use of a large mushroom-type N.O. (normally open) pushbutton rated for not less than 1 A /
24 Vdc is recommended. Verify continuity of the switch at its connection points before
installing.