GAMATRONIC ELECTRONIC INDUSTRIES LTD.
+
SA: 20, 30 and 40 kVA, Release 2.1
129
10. THE BUILT-IN WEB INTERFACE
The Power+ SA built-in Web interface enables you to monitor and control the Power+ SA
from a distance, using a PC over an Ethernet network. All that is required is an HTML
browser such as Microsoft’s Internet Explorer.
10.1 Preliminaries to use of the Web interface
To enable the Power+ SA Web interface:
1. Consult with your Network Administrator to obtain an IP address for your
Power+ SA, and the appropriate mask and gateway address.
2. Configure the Power+ SA with the IP address. This is done from the Power+ SA
main menu as follows:
a. Setup > (enter your password, then press Ent; default password is 8 left arrows) >
Service > SC2012 > Network.
b. From the Network menu, choose IP Address and enter the assigned IP address.
c. From the Network menu, choose Gateway and enter the assigned Gateway address.
d. From the Network menu, choose Mask and set the assigned subnet mask.
e. From the Network menu, choose Store to save the information just entered.
3. Connect the POWER+ SA to the local Ethernet network using the Ethernet (RJ45)
port on the left side of the UPS, behind a small removeable metal panel. This is the
port labeled “TCP/IP” in Figure 22 on page 30.
For neatness, the Ethernet cable for connection to the alarm connector can be
inserted through an opening on the rear left corner of the UPS, at about the same
height as the TCP/IP connector. See Figure 21.
4. On a computer terminal that has connectivity to the Power+ SA IP address, open a
Web browser and enter the Power+ SA IP address in the URL bar. For example,
type //192.102.2.130 and press Enter. You should see the Web interface main
screen (see Figure 282 below).