GAMATRONIC ELECTRONIC INDUSTRIES LTD.
78
+
SA: 20, 30, and 40 kVA, Release 2.1
3. Use the arrow keys to set BATEND and press Ent:
[Main Menu > SETUP > (password) > ALARM SET > FLOAT VOLT > BATEND]
FLOATING CHARGE ALARM SETUP
VOLTAGE SETTING: 340.0V
Figure 121: Set BATEND
4. Select BATLOW:
[Main Menu > SETUP > (password) > ALARM SET > FLOAT VOLT]
1> BATEND
2> BATLOW
3> ------
4> BAT-HI SELECT ITEM:1
Figure 122: Battery floating charge alarm setup menu
5. Use the arrow keys to set BATLOW and press Ent:
[Main Menu > SETUP > (password) > ALARM SET > FLOAT VOLT > BATLOW]
FLOATING CHARGE ALARM SETUP
VOLTAGE SETTING: 360.0V
Figure 123: Set BATLOW
6. Select BAT-HI:
[Main Menu > SETUP > (password) > ALARM SET > FLOAT VOLT]
1> BATEND
2> BATLOW
3> ------
4> BAT-HI SELECT ITEM:1
Figure 124: Battery floating charge alarm setup menu