SA: 20, 30, and 40 kVA, Release 2.1
9.11.1 Setting the Floating Charge
1. Select Charge:
[Main Menu > SETUP > (password) > Ent]
1> Alarm set 5> Time 9> Silicon
2> Module conf. 6> Site
3> Battery 7> Password #1
4> Charge 8> Service
Figure 197: Setup menu
2. Select Floating parameters setup.:
[Main Menu > SETUP > (password) > Charge]
1> -----
2> Floating parameters setup.
3> ----- (Eq:off)
4> ----- 1
Figure 198: Charge setup menu
3. Using the arrow keys, set the floating charge, press Ent, and then press Esc:
[Main Menu > SETUP > (password) > Charge > Floating parameters setup.]
Floating charge setup
Voltage setting: 864.0V
Figure 199: Set floating charge
9.11.2 Setting the Time
1. Select Time:
[Main Menu > SETUP > (password) > Ent]
1> Alarm set 5> Time 9> Silicon
2> Module conf. 6> Site
3> Battery 7> Password #1
4> Charge 8> Service
Figure 200: Setup menu