Step Operation Press Result
Increment key
or Decrement
key
Until you see Manual Reset.
Press the Function key to enter in the
configuration prompt of Manual Reset.
13 Configure
Manual Reset
Value
Increment key
or Decrement
key
Configure 0 for Manual Reset.
A Manual Reset of 0 is for no output bias
and requires that LSP2 = 0% of the Setpoint
Range. If bias is required, set the Manual
Reset value to equal the desired output bias
value.
Function key Configure the value 0 for Manual Reset.
14 Select
Algorithms set
up group
Setup key Until you see Algorithms set up group.
15 Select Control
Algorithm
Function key Enter in the first function prompt of the
Algorithms set up group: Control Algorithm
Press the Function key again to enter in the
first configuration prompt of Control
Algorithm.
16 Select PID A Increment key
or Decrement
key
Until you see the selection PID A.
Function key Select the selection PID A.
This is defining the back-up control
algorithm.
17 Select Tuning
set up group
Setup key Until you see Tuning set up group.
18 Configure PID
Set 1 Value
Function key Enter in the first function prompt of the
Tuning set up group.
Increment key
or Decrement
key
Until you see Gain 2.
Press the Function key again to enter in the
first configuration prompt of Gain 2.
19 Select Gain 2
Value
Increment key
or Decrement
key
Set the Gain 2 equal to:
205
Chapter 5 - Monitoring and Operating the Controller