4.1 Conformance with UL/cUL
This drive is listed under UL (Underwriters Laboratories Inc.) file number E141084 Vol.3
Sec.5.
USL, CNL Power conversion equipment (NMMS, NMMS7) Models AKD followed by B,
P, S, T, M or F, followed by 003, 006, 012, and 024, followed by 06 or 07, followed by addi-
tional suffixes.
USL
Indicates Investigated to United States Standard for Power Conversion Equipment, UL
508C, Third Edition, Revised February 15, 2008.
CNL
Indicates investigation to Canadian Standard for Industrial Control Equipment, CAN/CSA -
C22.2 No. 14-2005, Second Edition, Revised April 2008.
Note:
CNL = Canadian National Standards - Listed.
USL = United States Standards - Listed.
4.1.1 UL Markings
l Identification of the terminals on the controller are coded so they may be identified in the
instructions. The instructions shall identify power connections for power supply, load, con-
trol, and ground.
l Integral solid state short circuit protection does not provide branch circuit protection.
Branch circuit protection must be provided in accordance with the National Electrical
Code and any additional local codes, or the equivalent.
l This product is suitable for use on a circuit capable of delivering not more than 200,000
rms symmetrical amperes, 240 V (AKD-xzzz06) / 480 V (AKD-xzzz07) volts maximum,
when protected by fuses, or equivalent.
l The following fuse types are recommended:
Model Fuse class Rating Max. Fuse Rating
AKD-x00306 J 600 Vac, 200 kA 10 A
AKD-x00606 J 600 Vac, 200 kA 15 A
AKD-x01206 J 600 Vac, 200 kA 15 A
AKD-x02406 J 600 Vac, 200 kA 30 A
AKD-x00307 J 600 Vac, 200 kA 6 A
AKD-x00607 J 600 Vac, 200 kA 10 A
AKD-x01207 J 600 Vac, 200 kA 15 A
AKD-x02407 J 600 Vac, 200 kA 30 A
l These drives provide solid state motor overload protection at 125% of the rated FLA Cur-
rent.
l These devices are intended to be used in a pollution degree 2 environment.
l Maximum surrounding air temperature of 4C.
l Use minimum 75°C copper wire.
l These devices do not provide over temperature sensing.
l Use fuses only.
AKD Installation | 4 Approvals
Kollmorgen | May 2013 21

Table of Contents

Other manuals for Kollmorgen AKD

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Kollmorgen AKD and is the answer not in the manual?

Kollmorgen AKD Specifications

General IconGeneral
Control ModesTorque, Velocity, Position
Communication InterfacesEtherCAT, CANopen
Feedback OptionsResolver
SafetySTO (Safe Torque Off), SS1 (Safe Stop 1)
Protection FeaturesOvercurrent, Overvoltage, Undervoltage, Overtemperature
Operating Temperature Range0°C to 55°C
Humidity5% to 95% non-condensing