8.8.4.2 Single phase connection (AKD-x00306 to AKD-x01206 only)
l Directly to single-phase supply network ( p. 89
l Supply networks p. 89
l Leave L3 open circuit
l Filtering to be provided by the user.
l Fusing (such as fusible cut-outs) to be provided by the user p. 37
AKD-x00306 to AKD-x00606 (X3)
Pin Signal Description
4 L1 Line 1
5 L2 (N) Neutral or Line 2
7 PE Protective Earth
AKD-x01206 (X3)
Pin Signal Description
5 L1 Line 1
6 L2 (N) Neutral or Line 2
8 PE Protective Earth
AKD Installation | 8 Electrical Installation
Kollmorgen | May 2013 93