17 Function library
17.1 Function blocks | L_Counter_1
1327
Lenze · 8400 HighLine · Reference manual · DMS 12.0 EN · 06/2017 · TD23
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
General function
Every FALSE/TRUE edge at the bClkUp input causes the block to count upwards by "1".
Every FALSE/TRUE edge at the bClkDown input causes the block to count downwards by "1".
Function "Normal counting"
If the statement of the comparison mode selected in C01101/1
is true, the bCompare output is set
to TRUE.
Function "Auto reset"
If the statement of the comparison mode selected in C01101/1
is true, the bCompare output is set
to TRUE for 1 ms and the counter is reset to the wLdVal starting value.
Function "Manual reset"
If the statement of the comparison mode selected in C01101/1
is true, the bCompare output is set
to TRUE and the counter stops.
•Edges at bClkUp and bClkDown are ignored.
The counter must be reset via the bLoad input.
C01101/1 Selection of comparison operation
Lenze setting: Counter
content comparison value
0 Counter content comparison value
1 Counter content comparison value
2 Counter content = comparison value