Other functions for differential setpoint feedforward control
From version V12.00.00 onwards, the following additional functions are available for differential
setpoint feedforward control (torque feedforward control):
•In C00653/1
, the sensitivity of setpoint feedforward control can be adapted.
•In C00654/1
, alternatively to the nSpeedSetValue_a process signal, the new
nSpeedSetValueInertia_a process signal for the setpoint feedforward control can be selected at
the LS_MotorInterface
SB. Via the nSpeedSetValueInertia_a process signal, an optional input
value (e.g. setpoint of the position or process controller) for the torque feedforward control can
be specified.
•For bTorqueModeOn = TRUE, the setpoint feedforward control is added to the torque setpoint
nTorqueSetValue_a. In this way, feedforward control of torque is also possible for torque-
controlled operation (e.g. for winder applications).
Stop!
In the Lenze setting of C00654/1, the speed setpoint of the speed controller
(nSpeedSetValue_a) is used for the torque feedforward control which is why it is also
called "differential setpoint feedforward control". A very sharp change of the speed
setpoint at the speed controller thus causes a strong torque impulse at the machine!
Causes for a very sharp change of the speed setpoint of the speed controller:
A control creates the setpoint ramp itself and the speed setpoint is only written every
20 ms to the drive. (In this case, the speed setpoint is changed every 20 ms.)
Recommendation: Deactivate the torque feedforward control for the speed
setpoint in C00654/1
if the speed setpoint changes very sharply or the mass inertia
is unknown (e.g. in case of hoists)!
The reference speed C0011
is much higher than the rated motor speed set in C0087.
Recommendation: Deactivate the torque feedforward control for the speed
setpoint in C00654/1
if the reference speed C0011 5 times higher than the rated
motor speed C0087
.