8 Basic drive functions (MCK)
8.4 Basic settings
540
Lenze · 8400 HighLine · Reference manual · DMS 12.0 EN · 06/2017 · TD23
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
Re-activation after acknowledging the error
When the error has been acknowledged and the limit switch is still active, the following action is
required for a renewed activation of the monitoring depending on the operating mode:
Operating mode Action for (re) activation
Speed follower
Limit switch is activated and setpoint in direction of the activated limit switch is pending
Note: If the setpoint e.g. is specified via an analog potentiometer, potentiometer noise can
mean an unintentional setpoint causing the error to be set again.
Homing
Limit switch is activated and bHomStartStop = TRUE
Manual jog
Limit switch is activated and manual jog in direction of the activated limit switch
Positioning
Limit switch is activated and setpoint command has been transmitted
Stop
Setting of the operating mode
Position follower
Limit switch is activated and setpoint in direction of the activated limit switch is pending