C00321
C00322
Parameter | Name:
C00321 | Main program runtime
Data type: UNSIGNED_16
Index: 24254
d
= 5EBE
h
Display of the current and the maximum runtime of the main program in the inverter
Setting range (min. value | unit | max. value)
0 ms 65535
Subcodes Lenze setting Info
C00321/1 0 ms Curr. runtime of main program
C00321/2 0 ms Max. runtime of main program
Read access Write access CINH PLC STOP No transfer COM MOT Scaling factor: 1
Parameter | Name:
C00322 | Transmission mode CAN TxPDOs
Data type: UNSIGNED_8
Index: 24253
d
= 5EBD
h
TPDO transmission type according to DS301 V4.02
• The following transmission modes are supported:
• 0: Synchronous and acyclic
• 1 ... 240: Synchronous and cyclic
• 252: Synchronous - RTR only
• 253: Asynchronous - RTR only
• 254: Asynchronous - manufacturer-specific
• 255: Asynchronous - device-profile specific
• The basic setting for all PDOs is "Asynchronous - manufacturer-specific" (254).
• Illustration of the CANopen objects I-1800/2
... I-1803/2 (see DS301 V4.02).
"CAN on board" system bus
Setting range (min. value | unit | max. value)
0 255
Subcodes Lenze setting Info
C00322/1 254 Transmission mode CAN1 OUT
C00322/2 254 Transmission mode CAN2 OUT
C00322/3 254 Transmission mode CAN3 OUT
C00322/4 254 Transmission mode CAN4 OUT
• From version 15.00.00
Read access Write access CINH PLC STOP No transfer COM MOT Scaling factor: 1