230 SyncServer 600 Series User’s Guide 098-00720-000 Revision D1 – February, 2018
Chapter 6 Provisioning
Provisioning for SNMP
Each container contains the following sub-info in its own OID:
Alarm/Event ID
Date&Time
Severity
Alarm/Event Description
Index
Alarm Action
Sequence Number
The alarm OIDs are under 1.3.6.1.4.1.9070.1.2.5.7.4.1.
The Alarm/Event ID element should be used to determine which alarm or event was
generated. Alarm and Event IDs are listed in Appendix A, System Messages.
Provisioning to Generate v2 Traps
Use the set snmp trapversion command to provision the trap version to v2.
By default, the SyncServer S6x0 will generate v2 traps.
Note: The SNMP MIB can be downloaded from the SyncServer S6x0
on the Help web page. The LAST-UPDATED and REVISION fields in
the MIB can be used to determine the revision of the MIB. The
S650ALARM MIB description will also list which firmware the MIB
was made for. Older versions of the S650ALARM MIB will be
compatible with newer versions of firmware, but will not support
newer features.
Table 6-25. Provisioning to Generate v2 Traps
Method Steps Notes
Web Interface Network > SNMP Traps
1. Enter IP address for SNMP manager
2. Select SNMPv2c
3. Enter community name
4. Click “Save"
CLI n/a
Front Panel n/a