11
/
2017 Page 109 5IN2413 B
Quick keys Parameter Default Range
ZZZ

Day
Arm
Usually assigned to an infrequently used door, such as an emergency door
or a movable skylight. Used to alert the system user if a violation occurs
during the unset period (fault by day; Intruder at night), as follows:
With the system partially or fully armed (Stay or Away), the zone acts
as an intruder zone. A violation of this zone after the system is armed
or during the exit delay time period causes an immediate intrusion
alarm.
With the system disarmed, a violation of this zone attempts to alert the
user by causing the POWER/ indicator on all keypads to flash
rapidly. This directs the user to view the system's trouble indications.
Optionally, such a violation can be reported to the monitoring station
as a zone trouble. See Appendix E: Report Codes Miscellaneous
(page.238).
ZZZ

24 Hours
Usually assigned to protect non-movable glass, fixed skylights, and
cabinets (possibly) for shock detection systems.
A violation of such a zone causes an instant intrusion alarm, regardless of
the system's state
ZZZ

Fire
For smoke or other types of fire detectors. This option can also be used for
manually-triggered panic buttons or pull stations (if permitted), as follows:
If violated, it causes an immediate fire alarm, and the Fire/ indicator
is lit (steady).
A fault in the wiring (wire open) to any fire zone causes a Fire Trouble
signal (a rapid flashing of the keypads' Fire / indicator). A short in
the wires will cause an immediate alarm.
ZZZ

Panic
Used for external panic buttons and wireless panic transmitters.
If violated, an immediate panic alarm is sounded (if the zone sound is not
defined as silent or audible panic system control is enabled), regardless of
the system’s state, and a panic report is sent to the monitoring station. An
alarm display will not appear on the keypads. If violated, an immediate
panic alarm is sounded, regardless of the system's state.