11
/
2017 Page 115 5IN2413 B
Zones Parameters By Category Loop Response
Quick keys Parameter Default Range

Loop Response
The Loop Response menu enables you to set the different times for
which a zone violation must exist before the zone will trigger an alarm
condition.
1. Select the zone (ZZZ) and then press OK.
2. Then scroll to select a loop response type:
Normal: 400 ms (milliseconds).
Long: 1 second
Fast: 10 ms (milliseconds).
Extra Fast: 1 ms (millisecond). This loop response is usually used
for shutters or other devices that require very quick responses
3. Press OK.
Zones Parameters By Category Advanced
The following Advanced zone parameters are available for configuration:
Advanced
Bus Zone Parameters
Wireless Zone Configuration
Quick keys Parameter Default Range

Advanced

Forced arming
This option enables or disables the use of forced arming for each of the
system's zones, as follows:
If forced arming is enabled for a particular zone, it allows the system
to be armed even though this zone is faulty.
When a zone(s) enabled for forced arming is faulted, the red LED
blinks during disarm period.
After arming, all zones enabled for forced arming are bypassed at the
end of the exit delay time period (see  page 78).
If a faulted zone (one enabled for force arming) is secured during the
armed period, it will no longer be bypassed and will be included
among the system's armed zones.