11
/
2017 Page 94 5IN2413 B
System Controls PD6662:2010 (BS 8243:2010)
Quick keys Parameter Default Range

PD6662:2010 Prog.
(BS 8243:2010 Prog.)
If the PD6662:2010 (BS 8243:2010) standard has been selected (see procedure
on page 100), then the configurable controls for this standard (listed below)
can be set as needed. NOTE: For the non-configurable "Hold-Up Alarm
Confirmation" parameter, see page 100.

Bypass Exit/Entry
Yes Yes/No
YES: It is possible for the user to bypass an Exit/Entry zone.
NO: An Exit/Entry zone cannot be bypassed.

Entry Disable
No Yes/No
YES: Alarm confirmation process will be disabled when entry time starts.
NO: Alarm confirmation process will start when the entry time starts.

Route Disable
No Yes/No
YES: The panel disables the entry route zones (EX/EN, EX (OP)/EN,
followers and Final Exit) from participating in the alarm confirmation
process when the entry time starts.
Note
Sequential confirmation can still be established from two confirmed zones,
located off the entry route.
NO: The entry route zones will participate in the alarm confirmation
process when the entry time starts.

Installer
Confirmation
No Yes/No
YES: An installer confirmation is required in order to reset the system after
a confirmed alarm. The system cannot be armed until an installer reset
confirmation is performed. The reset can be done by entering the Anti Code
or entering the installation mode or by performing an “Installer reset” from
the keypad.
NO: Any means can be used to arm or disarm the system (keypad, remote
phone operation etc.).