3.39
Date Code 20060320 Instruction Manual SEL-311C Relay
Distance, Out-of-Step, Overcurrent, Voltage, Synchronism Check, and Frequency Elements
Time-Overcurrent Elements
Accuracy
Pickup
±0.05 A secondary and ±3% of setting
(5 A nominal phase current inputs, IA, IB, IC)
±0.01 A secondary and ±3% of setting
(1 A nominal phase current inputs, IA, IB, IC)
Curve Timing
±1.50 cycles and ±4% of curve time for currents
between (and including) 2 and 30 multiples of pickup