EasyManua.ls Logo

Schweitzer Engineering Laboratories SEL-311C - Figure 13.8 Phase Distance Element Test Voltage Signals

Schweitzer Engineering Laboratories SEL-311C
748 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
13.37
Date Code 20060320 Instruction Manual SEL-311C Relay
Testing and Troubleshooting
Test Procedures
Figure 13.8 Phase Distance Element Test Voltage Signals
Step 13. When the magnitude of V
BC
calculated above lies between 67
and 35 volts, use β = 150° and |V
B
| = |V
C
| = |V
BC
|.
Step 14. When the magnitude of V
BC
calculated above is greater than
67 volts, use |V
B
| = |V
C
| = 67 V.
Step 15. Calculate the angle β through use of Equation 13.38.
Step 16. When the magnitude of V
BC
calculated above is less than
35 volts, use |V
B
| = |V
C
| = 35 V.
Step 17. Calculate the angle β through use of Equation 13.38.
Equation 13.38
Step 18. Select V
A
= 67 0° volts. For the Zone 2 B-C element test,
based upon the example settings, the magnitude of V
BC
equals
46.8 volts. From the equations above, select the following test
voltage magnitudes and angles.
V
A
= 67.0 V 0° volts
V
B
= 46.8 –150° volts
V
C
= 46.8 ∠150° volts
The phase distance element maximum reach is measured when
faulted phase-to-phase current lags faulted phase-to-phase
voltage by the distance element maximum torque angle. In the
SEL-311C, the phase distance element maximum torque angle
is defined by the angle of the relay Z1ANG setting.
For the example relay settings, I
BC
should lag V
BC
by 83.97°.
Based upon the test voltages selected above, V
BC
lags V
A
by
90°, so I
BC
should lag V
A
by 173.97°.
As stated above, the phase distance elements are supervised by
the negative-sequence directional element. It is important to
check the negative-sequence quantities applied and verify that
b
b
b
b
Vb
Vc
Vbc
Va
β 180° a sin
V
BC
2V
C
()
-------------------------
deg=

Table of Contents

Related product manuals