7.40
SEL-311C Relay Instruction Manual Date Code 20060320
Inputs, Outputs, Timers, and Other Control Logic
Rotating Default Display (Only on Models With LCD)
This results in the continual display of text setting DP5_1 on the front-panel
display:
This can also be realized with the following settings:
DP5 = 0 (set directly to logical 0)
DP5_1 = (“blank”)
DP5_0 = LINE 1204 (displays when DP5 = logical 0)
This results in the continual display of text setting DP5_0 on the front-panel
display:
Active Setting
Group Switching
Considerations
The SELOGIC control equation display point settings DPn (n = 1–16) are
available separately in each setting group. The corresponding text settings
DPn_1 and DPn_0 are made only once and used in all setting groups.
Refer to Figure 7.30 and the following discussion of an example setting group
switching discussion.
Setting Group 1 Is the Active Setting Group
When setting Group 1 is the active setting group, optoisolated input IN102
operates as a reclose enable/disable switch with the following settings:
SEL
OGIC control equation settings:
79DTL = !IN102 + ... [= NOT(IN102) + ...; drive-to-lockout setting]
DP1 = IN102
Text settings:
DP1_1 = 79 ENABLED (displayed when DP1 = logical 1)
DP1_0 = 79 DISABLED (displayed when DP1 = logical 0)
Reclosing Relay Enabled
In Figure 7.30, optoisolated input IN102 is energized to enable the reclosing
relay, resulting in:
DP1 = IN102 = logical 1
This results in the display of corresponding text setting DP1_1 on the front-
panel display:
LINE 1204
LINE 1204
79 ENABLED