D.12
SEL-311C Relay Instruction Manual Date Code 20060320
Configuration, Fast Meter, and Fast Operate Commands
Message Definitions
A5ED Fast Operate
Reset Command
The Fast Operate Reset commands take the form shown in Table D.12.
ID Message
In response to the ID command, the relay sends the following information
described below.
<STX>"FID=SEL-311C-Rrrr-Vv-Zzzzzzz-Dyyyymmdd","aaaa"<CR><LF>
"CID=cccc","aaaa"<CR><LF>
"DEVID=[TID SETTING]","aaaa"<CR><LF>
"DEVCODE=48","aaaa"<CR><LF>
"PARTNO=[PARTNO SETTING]","aaaa"<CR><LF>
"CONFIG=bbbbbb","aaaa"<CR><LF><ETX>
The ID message is available from Access Level 1 and higher.
DNA Message
In response to the DNA command, the relay sends names of the Relay Word
bits transmitted in the A5D1 message. The first name is associated with the
MSB, the last name with the LSB. These names are listed in Table 9.5. The
DNA command is available from Access Level 1 and higher.
Per Fast Operate reset code, repeat:
00 Fast Operate reset code (e.g., “00” for target reset)
54415220520000 Fast Operate reset description string (e.g., “TAR R”)
xx Checksum
Table D.11 A5CD Fast Operate Reset Definition Block (Sheet 2 of 2)
Data Description
Table D.12 A5ED Fast Operate Reset Command
Data Description
A5ED Command
06 Message Length—always 6
00 Operate Code (e.g., “00” for target reset, “TAR R”)
01 Operate Validation 1 + (Operate Code • 4)
xx Checksum
where:
rrr = the firmware revision
zzzzzz = settings and protocol version numbers
cccc = the 4-digit firmware checksum
yyyy = the 4-digit year code
mm = the 2-digit month code
dd = the 2-digit day code
bbbbbb = the 6-digit configuration code
aaaa = an ASCII representation of the 2-byte checksum for each
line
FID = the Firmware identification string
CID = the 4-digit hexadecimal checksum of the firmware
DEVID = the text from the Relay Identification (RID) setting
DEVCODE = the Modbus Device ID Code for the SEL-311C
PARTNO = the part number that matches the Model Option Table
number
CONFIG = the configuration string used for SEL internal use only