EasyManua.ls Logo

Schweitzer Engineering Laboratories SEL-311C - Table 14.11 SEL OGIC Equivalent to SEL-221 H Relay Word Bits

Schweitzer Engineering Laboratories SEL-311C
748 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
14.22
SEL-311C Relay Instruction Manual Date Code 20060320
Application Settings for SEL-221 Series Relays
SEL-221H to SEL-311C Settings Conversion Guide
Table 14.11 shows all SEL-221H Relay Word bits, and an approximate
equivalent SEL-311C SEL
OGIC expression, when setting APP = 221H in the
SEL-311C. Table 14.10 shows each SEL-221H Mask Logic Setting and the
equivalent SEL-311C SEL
OGIC control equation. To convert an SEL-221H
Mask Logic Setting to a SEL
OGIC control equation, logically OR each
appropriate SEL-221H Relay Word bit equivalent expression (Table 14.11)
and enter the resultant expression in the related SEL
OGIC control equation
listed in Table 14.10.
Ta ble 1 4.11 SE LOGIC Equivalent to SEL-221H Relay Word Bits
SEL-221H Relay Word Bit
Equivalent SEL-311C
SEL
OGIC Expression
1ABC M1P * !32QF
2ABC M2P * !32QF
3ABC M3P * !32QF if DIR3 = F
M3P * 32QR if DIR3 = R
4ABC None
LOP ILOP
50H 50P1
50M 50P2
50L None
51NT 51GT
67N1 67G1
67N2 67G2
67N3 67G3
51NP 51G
Z1P M1P
Z2P M2P
Z3P M3P
Z2PT M2PT
Z3PT M3PT
Z3RB Z3RB
KEY KEY
50MF SV1T (SV1 = 50P1 * ILOP)
PTEE None
ECTT ECTT
DF 32GF
ALRM ALARM
TRIP TRIP or OUT101 or OUT102
TC OC
DT IN101
52BT SOTFE
WFC WFC
Z2GT 67G2T
Z3GT 67G3T

Table of Contents