EasyManua.ls Logo

Schweitzer Engineering Laboratories SEL-311C - A5 E0 Fast Operate Remote Bit Control; Table D.9 A5 E0 Fast Operate Remote Bit Control

Schweitzer Engineering Laboratories SEL-311C
748 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
D.10
SEL-311C Relay Instruction Manual Date Code 20060320
Configuration, Fast Meter, and Fast Operate Commands
Message Definitions
A5E0 Fast Operate
Remote Bit Control
The external device sends the message shown in Tabl e D.9 to perform a
remote bit operation.
The relay performs the specified remote bit operation if the following
conditions are true:
1. The Operate code is valid.
2. The Operate validation = 1 + (Operate code • 4).
3. The message checksum is valid.
4. The FASTOP port setting is set to Y.
5. The relay is enabled.
Remote bit set and clear operations are latched by the relay. Remote bit pulse
operations assert the remote bit for one processing interval (1/4 cycle).
4A Operate code, pulse remote bit RB11
0B Operate code, clear remote bit RB12
2B Operate code, set remote bit RB12
4B Operate code, pulse remote bit RB12
0C Operate code, clear remote bit RB13
2C Operate code, set remote bit RB13
4C Operate code, pulse remote bit RB13
0D Operate code, clear remote bit RB14
2D Operate code, set remote bit RB14
4D Operate code, pulse remote bit RB14
0E Operate code, clear remote bit RB15
2E Operate code, set remote bit RB15
4E Operate code, pulse remote bit RB15
0F Operate code, clear remote bit RB16
2F Operate code, set remote bit RB16
4F Operate code, pulse remote bit RB16
00 Reserved
checksum 1-byte checksum of all preceding bytes
Table D.8 A5CE Fast Operate Configuration Block (Sheet 2 of 2)
Data Description
Table D.9 A5E0 Fast Operate Remote Bit Control
Data Description
A5E0 Command
06 Length
1 byte Operate code:
00–0F clear remote bit RB1–RB16
20–2F set remote bit RB1–RB16
40–4F pulse remote bit for RB1–RB16 for one processing interval
1 byte Operate validation: 1 + (Operate code • 4)
checksum 1-byte checksum of preceding bytes

Table of Contents