EasyManua.ls Logo

Schweitzer Engineering Laboratories SEL-311C - Convert SEL-221 G-5 Settings to SEL-311 C Settings; Table 14.5 SEL-311 C Settings Calculated from SEL-221 G-5 Settings; Convert SEL-221 G-5 Primary Quantities to SEL-311 C Secondary Quantities

Schweitzer Engineering Laboratories SEL-311C
748 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
14.12
SEL-311C Relay Instruction Manual Date Code 20060320
Application Settings for SEL-221 Series Relays
SEL-221G-5 to SEL-311C Settings Conversion Guide
Convert SEL-221G-5
Primary Quantities to
SEL-311C Secondary
Quantities
All SEL-221G-5 current settings must be converted from primary to
secondary amps to be used in the SEL-311C. Divide the SEL-221G-5 current
setting by the current transformer ratio setting (CTR) to make the change.
SEL-221G-5 impedance settings must be converted from percent of primary
line impedance to secondary impedance in ohms. For example, the Zone 1
distance setting in the SEL-311C (Z1P) is calculated as
Equation 14.2
Convert SEL-221G-5
Settings to SEL-311C
Settings
Table 14.5 shows all the SEL-311C settings that must be entered for the relay
to perform protection similar to the SEL-221G-5 when APP = 221G5.
Calculate each SEL-311C setting from SEL-221G-5 settings using the
formula shown. Instruction manual references are to subsection headings
rather than to section headings.
where:
Z1% = the SEL-221G-5 distance reach setting
Z1MAG = the SEL-311C positive-sequence line impedance setting
in secondary ohms
Z1P = the SEL-311C Zone 1 reach setting in secondary ohms
Z1P
Z1%
100
------------
Z1MAG=
Table 14.5 SEL-311C Settings Calculated From SEL-221G-5 Settings (Sheet 1 of 3)
SEL-311C
Setting
a
Calculated From SEL-221G-5 Settings
SEL-311C Instruction
Manual Section
SEL-221G-5 Instruction
Manual Section
RID None Settings Sheets for the
SEL-311C Relay
Section 3—Set n
TID = ID
CTR = CTR Settings Sheets for the
SEL-311C Relay
Section 5—Choosing Current and
Potential Transformers
CTRP = CTR
PTR = PTR
PTRS = PTR
Z1MAG
Settings Sheets for the
SEL-311C Relay
Section 5—Choice of
Line Impedances
Z1ANG
Section 5—Choice of Maximum
Torque Angle (MTA)
Z0MAG
Z0ANG
LL = LL Settings Sheets for the
SEL-311C Relay
APP None
EFLOC = LOCAT Settings Sheets for the
SEL-311C Relay
Section 2—Fault Locator
ELOP
N
Y
= LOPE
= N
= Y
Loss-of-Potential Logic on
page 4.1
Section 5—Loss-of-Potential Logic
R1
2
X1
2
+()=
CTR
PTR
------------
Arc tan
X1
R1
-------
= (degrees) = MTA
R0
2
X0
2
+()=
CTR
PTR
------------
Arc tan
X0
R0
-------
= (degrees)

Table of Contents

Related product manuals