H.10
SEL-311C Relay Instruction Manual Date Code 20060320
Setting SELOGIC Control Equations
Processing Order and Processing Interval
Processing Order and Processing Interval
The relay elements and logic (and corresponding SELOGIC control equation
settings and resultant Relay Word bits) are processed in a predetermined order.
They are processed every quarter-cycle (1/4-cycle), and the Relay Word bit
states (logical 1 or logical 0) are updated with each quarter-cycle pass. Thus,
the relay-processing interval is 1/4-cycle. Once a Relay Word bit is asserted, it
retains the state (logical 1 or logical 0) until it is updated again in the next
processing interval. Logical outputs of SEL
OGIC control equations may be
delayed by 1/4-cycle due to relay element processing order.