SEL-311C Relay Instruction Manual Date Code 20060320
Application Settings for SEL-221 Series Relays
SEL-221-16 to SEL-311C Settings Conversion Guide
Convert SEL-221-16
Output Mask Logic
Settings to SELOGIC
Control Equations
See Programmable Output Contact Mask Settings in Section 5: Applications
in the SEL-221-16 Instruction Manual for a description of output masks. In
the SEL-311C, output masks are replaced by SEL
OGIC control equations as
shown in Table 14.29.
Table 14.30 shows all SEL-221-16 Relay Word bits, and an approximate
equivalent SEL-311C SEL
OGIC expression, when setting APP = 221-16 in the
SEL-311C. Table 14.29 shows each SEL-221-16 Mask Logic Setting and the
equivalent SEL-311C SEL
OGIC control equation. To convert an SEL-221-16
Mask Logic Setting to a SEL
OGIC control equation, logically OR each
51GTC
(= 1
(= 32GF
= 51NTC (51GTC is an SEL-311C
SEL
OGIC setting.)
= N)
= Y)
79OI1 = 79OI1 Section 6: Close and Reclose
Logic
Section 5—Reclose Logic
79RSD = 79RS
79RSLD = 79RS
52AEND = 52BT (Pickup) Switch-Onto-Fault Trip Logic
on page 5.7
Section 5—52BT Setting (52BT)
and Switch-Onto-Fault Protection
SOTFD = 52BT (Dropout)
TDURD = TDUR Unlatch Trip on page 5.4 Section 5—Trip Duration Timer
(TDUR)
SV1PU = A1TP SEL
OGIC Control Equation
Variables/Timers on page 7.28
Section 2—Miscellaneous Timers
SV1DO = A1TD
a
SEL-311C phase-to-phase fault detector settings (50PP1, 50PP2, and 50PP3) are set to their minimum values and hidden. This
corresponds to SEL-221-16 setting 50P.
SEL-311C phase-to-ground and residual fault detector settings (50L1, 50L2, 50L3, 50GZ1, 50GZ2, and 50GZ3) are set to their minimum
values and hidden. This corresponds to SEL-221-16 setting 50NG.
SEL-221-16 function “Remote End Just Opened” (REJO) is not implemented in the SEL-311C.
b
Curve U1 in the SEL-311C is slightly different from curve 1 in the SEL-221-16. Time dial adjustments may be necessary.
Table 14.28 SEL-311C Settings Calculated From SEL-221-16 Settings (Sheet 3 of 3)
SEL-311C
Setting
a
Calculated From SEL-221-16 Settings
SEL-311C Instruction
Manual Section
SEL-221-16 Instruction
Manual Section
Table 14.29 SEL-311C SELOGIC Control Equation Equivalent to Each
SEL-221-16 Mask Logic Setting
SEL-221-16 Settings Mask SEL-311C SELOGIC Control Equations
MTU TR
MPT None
MTB None
MTO TRSOTF
MA1 OUT104
MA2 OUT105
MA3 OUT106
MA4 OUT107
MRI 79RI
MRC 79DTL