Schweitzer Engineering Laboratories SEL-311C - Figure 4.10 Zero-Sequence Voltage-Polarized Directional Element for Ground Distance and Residual Ground Overcurrent Elements

Schweitzer Engineering Laboratories SEL-311C
748 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
4.15
Date Code 20060320 Instruction Manual SEL-311C Relay
Loss-of-Potential, CCVT Transient Detection, Load-Encroachment, and Directional Element Logic
Directional Control for Ground Distance and Residual Ground Overcurrent Elements
Note: 1 Z1L = One ohm at the zero-sequence line angle.
q From Figure 4.7; w from Figure 4.1; e from Figure 4.8; r to Figure 4.12.
Figure 4.10 Zero-Sequence Voltage-Polarized Directional Element
for Ground Distance and Residual Ground Overcurrent Elements
I
0
V
0
If Z0F Setting > 0, Forward Threshold = 1.25 • Z0F — 0.25 •
I
0
V
0
If Z0F Setting 0, Forward Threshold = 0.75 • Z0F — 0.25 •
Forward Threshold:
I
0
V
0
If Z0R Setting < 0, Reverse Threshold = 1.25 • Z0R + 0.25 •
I
0
V
0
If Z0R Setting 0, Reverse Threshold = 0.75 • Z0R + 0.25 •
Reverse Threshold:
Direction Element Characteristics
R0
X0
Forward Threshold
Reverse Threshold
Z0 PLANE
enable output
r
R32V
(Reverse)
F32V
(Forward)
q
50GF
Enable
Forward
Threshold
q
32VE
w
ILOP
Reverse
Threshold
q
50GR
Re[3V
0
•(I
G
•1
Z0L)*]
|I
G
|
2
Z0 =
I
G
(residual)
(I
G
= 3I
0
)
3V
0
Relay
Word
Bits
Relay
Word
Bit
Relay
Word
Bits
Relay
Word
Bit
e
Best Choice Ground
Directional Logic