Date Code 20060320 Instruction Manual SEL-311C Relay
Appendix G
SEL Synchrophasors
Overview
The SEL-311C provides Phasor Measurement Control Unit (PMCU)
capabilities when connected to an IRIG-B time source with an accuracy of
±10 µs or better. Synchrophasor data are available via the MET PM ASCII
command and the SEL Fast Message Unsolicited Write message.