12.31
Date Code 20060320 Instruction Manual SEL-311C Relay
Standard Event Reports and SER
Example Sequential Events Recorder (SER) Report
Example Sequential Events Recorder (SER) Report
The following example sequential events recorder (SER) report in Figure 12.6
also corresponds to the example standard 15-cycle event report in Figure 12.3.
=>>SER <Enter>
SEL-311C POTT Date: 10/14/99 Time: 08:56:47.400
EXAMPLE: BUS B, BREAKER 3
FID=SEL-311C-R100-V0-Z001001-D19991118 CID=B142
# DATE TIME ELEMENT STATE
14 10/14/99 08:53:34.083 IN101 Asserted
13 10/14/99 08:53:34.926 51G Asserted
12 10/14/99 08:53:34.930 50P1 Asserted
11 10/14/99 08:53:34.930 M2P Asserted
10 10/14/99 08:53:34.930 M1P Asserted
9 10/14/99 08:53:34.930 OUT101 Asserted
8 10/14/99 08:53:34.930 OUT102 Asserted
7 10/14/99 08:53:35.026 50P1 Deasserted
6 10/14/99 08:53:35.026 M1P Deasserted
5 10/14/99 08:53:35.026 51G Deasserted
4 10/14/99 08:53:35.030 M2P Deasserted
3 10/14/99 08:53:35.030 IN101 Deasserted
2 10/14/99 08:53:35.079 OUT101 Deasserted
1 10/14/99 08:53:35.079 OUT102 Deasserted
=>>
Figure 12.6 Example Sequential Events Recorder (SER) Event Report
The SER event report rows in Figure 12.6 are explained in Table 12.7,
numbered in correspondence to the # column. The circled, numbered
comments in Figure 12.3 also correspond to the # column numbers in
Figure 12.6. The SER event report in Figure 12.6 may contain records of
events that occurred before and after the standard event report in Figure 12.3.
Table 12.7 Explanation of Row Entries for Figure 12.6
SER
Row No.
Explanation
14
IN101 is asserted when the circuit breaker closes.
Related Setting: 52A = IN101
13
Time-overcurrent element 51G asserts.
12
Instantaneous-overcurrent element 50P1 asserts.
11
Phase-distance element M2P asserts.
10
Phase-distance element M1P asserts. This is an instantaneous trip condition.
Related setting: TR = M1P + Z1G + M2PT + Z2GT + 51GT + 51QT
9, 8 Outputs OUT101 and OUT102 assert.
Related setting: OUT101 = TRIP
OUT102 = TRIP
7, 6, 5, 4 Elements 50P1, M1P, 51G , and M2P deassert as the circuit breaker opens.
3
IN101 deasserts when the circuit breaker opens.
Related Setting: 52A = IN101
2, 1 Outputs OUT101 and OUT102 deassert.