7.12
SEL-311C Relay Instruction Manual Date Code 20060320
Inputs, Outputs, Timers, and Other Control Logic
Remote Control Switches
remote bit is deasserted to logical 0) before a settings change or an active
setting group change, it comes back in the OFF position (corresponding
remote bit is still deasserted to logical 0) after the change.
If settings are changed for a setting group other than the active setting group,
there is no interruption of the remote bits (the relay is not momentarily
disabled).